Chiller - fancoil system. From Wikipedia - the free encyclopedia
Chiller is a water-cooling machine which use vapor compression or absorption refrigeration cycle. Chilled water may be used with the fan-coil system or for equipment cooling. During the cooling chiller generates excess heat that have to be abstracted in the environment.
Chiller - fancoil system is a centralized multi zone air-conditioning system. This system use a liquid which circulates between chiller and heat exchangers (local fan-coils) with a relatively low pressure. As a liquid may be used water or water-glycol mix. Besides chiller and fan-coils this system consists of pump station and automatic control.
Terminology:
Translation for «chiller» is missed in GOST 22270-76 «Equipment for air conditioning, ventilation and heating». For the «fan coil unit» - fan closer (the closer is worked with the built-in fan local recirculation and flow in the room is a mixture of indoor air with outdoor air which having passed pre-processing in the central air conditioner and also heating and/or cooling air)
Advantages:
Advantages in Advantages in comparison with split-systems.
- Scalability. Number of fan-coils is limited only by cooling capacity of chiller.
- The minimum volume and area. The air conditioning system of a large building may contain a single chiller, which occupies a minimum volume and area. Exterior of building staying the same.
- Practically unlimited distance between chiller and fan coil units. Length of tracks may reach hundreds of meters. Heat losses per meter are much lower in comparison with a refrigerant gas system.
- The piping cost. For the piping uses standard water pipes and valves. Adjustment of water system much easier then refrigerant gas system.
- Safety. Refrigerant gas uses only in chiller which usually placed outdoor. Water circuit has valves to prevent the accidents.
Disadvantages:
The system chiller-fan coil units are more effective in electricity consumption than roof-mounted systems but less economy in comparison with systems with variable refrigerant flow (VRF). However maximum capacity VRF-system is limited.
Failures:
- Freon leak. Freon leakage may be caused by non-hermetic connections of the refrigerant circuit.
- Compressor breakdown. This may be caused by electrical reasons or mechanical damages of piston group.
- Moisture in the refrigeration circuit. Moisture in the refrigeration circuit may appears with damages in the evaporator.
Notes:
- GOST 22270-76 (ST SEV 2145-80). USSR State standards. 76 «Equipment for air conditioning, ventilation and heating»pdf